undefined
undefined
undefined
+
  • undefined
  • undefined
  • undefined

ZXDU48 B600 60A 2*RETIF ZXD1500 48V DC V5.0

Focado em fornecer equipamentos de comunicação por fibra óptica e produtos de apoio a clientes globais

Categoria:

  • Descrição
  • ZXDU48 B600 Overview

    ZXDU48 B600 is a 1U high/19 inch wide embedded communication DC power system can be insert 1*monitoring module ZTE CSU520Y 2*rectifier module ZTE ZXD1500. which is -48 V Series communication equipment power supply.
    Adopt single-phase three-wire AC input mode (L/N/PE), suitable for 220 V/380 V power grid. At the same time, compatible with 110V dual live wire access.
    Fully configured with 2 ZXD1500 (V5.0) rectifiers, rated output power is 3200 W, maximum output current is 60A/53.5 V DC.
    The ZXDU48 B600 DC power system can be installed into a 19-inch cabinet to supply power to -48V communication devices.


    Specification

    Item

     Description

    Operating temperature

    -33℃ to +55℃

     

    Sheds the load when they system operates in a temperature higher than 55℃

    Powers off automatically when the system temperature is higher than 75℃

    Storage temperature-45℃ to +70℃
    Relative humidity5% to 95% (non-condensing). It is recommended that the relative humidity is in the range of 40% to 60%
    Altitude

    0m to 2000m: Outputs in full power

     

    2000m to 3000m: Derated by 1% for every 100m increase of altitude

    Space requirement

    The system must be installed in a 19-inch cabinet or rack.

     

    The system must be horizontally installed. The cabinet must be definitely vertical. No bump is allowed.

    There should be no liquid or conductive objects within, or dropping into the cabinet.

    The system must not be installed near any water, corrosive gas, or explosive materials.

    There should be no conductive dust or electromagnetic interference in the vicinity.

     System capacity3200W/66A. Two ZXD1500 rectifiers are required for full configuration
     System efficiencyPeak efficiency: 95%
    Power limitation based on the input voltageAC input ≤85 V± 5 VThe output power of the rectifier is 0%.
    AC input (85 V±5 V) to 110 VThe power drops linearly. The output power of the rectifier ranges from 40% to 60% of the overall power.
    AC input 110 V to 176 VThe power drops linearly. The output power of the rectifier ranges from 60% to 100% of the overall power.
    AC input 176 V to (305 V±5 V)The output power of the rectifier is 100%.
    AC input >305 V±5 VThe output power of the rectifier is 0%.
    Power limitation based on the temperatureAmbient temperature: -33℃ to +55℃The output power of the rectifier is 100%
    Ambient temperature: +55℃ to +75℃ The output power decreases linearly as the temperature rises. When the environmental temperature reaches 70°C, the output power is no lower than 62.6% of the maximum power.
    Ambient temperature: >+75°C The output power of the rectifier is 0% (power-off protection)
    Over all noise (sound pressure)≤68 dB(A)
    Network architecture for monitoringRS232 ports connected in series
     Mean time between failuresMTBF≥3.2x 10⁵ h
    Design life 10 years to 15 years
    Input AC featuresAC input mode Three-wire single-phase system (LN/PE). Compatible with dual-live wires (L1/L2/PE)
    Input AC voltage

    Rated phase-to-neutral voltage: 200 V to 240 V

     

    Range of phase-to-neutral voltage: 85 V to 295 V

    Input frequency

    Rated frequency: 50 Hz/60 Hz

     

    Frequency range: 45 Hz to 66Hz

    Input PFThe PF is no lower than 0.996 at the rated load.
    Total harmonic distortion THD≤5% when the system operates at a power ranging from 30% to 100% of the rated power.
    AC lightning protection A lightning protection module is embedded in the rectifier.
     AC power distributionNumber of AC inputs 1
    AC input circuit breaker 3xrimping terminals
    Stanby AC output –
    Protection featureAC overvoltage protection The overvoltage protection takes effect when the single-phase input voltage is higher than the AC overvoltage protection threshold.
    AC undervoltage protection The undervoltage protection takes effect when the single-phase input voltage is lower than the AC under voltage protection threshold.
    Output DC propertiesRated DC output voltage -53.5 V DC
    Range of the DC output voltage Continuously adjustable from -41 V to -58 V (adjust by the CSU)
    Voltage drop in the cabinet ≤500 mV
    Regulated voltage precision≤0.6%
    Psophometrically weighted noise voltage≤2 mV
    DC lightningMaximum current of the lightning arrester: Imax = 3 kA (8/20 μs)
    DC power distributionBattery inputsOne input. 1 x 30 A, configured with a 40 A fusible link
    Protection featurePower-off protection modeBattery Low Voltage Disconnect (BLVD)
    DC load outputsTwo outputs. 2 x 20 A, configured with a 40 A fusible link
    DC overvoltage protectionThe overvoltage protection takes effect when the output voltage is higher than the DC overvoltage protection threshold.
    DC undervoltage protectionThe undervoltage protection takes effect when the output voltage is lower than the DC overvoltage protection threshold.
    Battery undervoltage protectionThe power-off protection takes effect when the battery voltage is lower than the power -off voltage protection threshold.
    Dimensions

    1U height / 19-inch width

     

    43.6 mm x 482.6 mm x 260 mm (Height x Width x Depth)

    Overall weight (including the rectifiers)Around 8 kg
    Installation modeEmbedded in a 19-inch cabinet

Consulta sobre o produto

Tem alguma dúvida sobre a compra de um produto ou solução que lhe interessa? Preencha o formulário e responderemos em até 7 dias úteis.

Enviar

Produtos Mais Recentes